Rika Sensor is a weather sensor manufacturer and environmental monitoring solution provider since 2010
PRODUCT DESCRIPTION
The RK500-30 Corrosion Rate Sensor provides online corrosion monitoring for data center liquid-cooling loops and industrial water systems. It combines Linear Polarization Resistance (LPR) and Electrochemical Impedance Spectroscopy (EIS) to monitor localized pitting and average corrosion rates. The listed media include deionized water, PG25 and EG25. With automatic temperature compensation, a 0–1 mm/year range and 0.0001 mm/year resolution, it delivers corrosion data through simultaneous 4–20 mA and RS485 outputs, with Modbus communication supported on RS485. Its 316L body, EPDM seal and IP68-rated probe suit in-line monitoring applications. Configurations are available for stainless steel, aluminum and copper piping; confirm the pipeline material when ordering.
SPECIFICATIONS
| Item | Technical Specification |
|---|---|
| Main material | 316L |
| Measurement principle | LPR (Linear Polarization Resistance) & EIS (Electrochemical Impedance Spectroscopy) |
| Compatible pipeline material | Stainless Steel (Default), Aluminum, Copper |
| Applicable medium | Deionized water, PG25, EG25 |
| O-ring material | EPDM |
| Measurement range | 0 ~ 1 mm/a |
| Accuracy | ±0.001 mm/a |
| Resolution | 0.0001 mm/a |
| Supply voltage | 7-30VDC |
| Output signal | 4-20mA & RS485 at the same time |
| Response time | 1s |
| Drift | ≤ 0.3% FS / 24h |
| Pressure resistance | 1MPa (10Bar) |
| Operating temperature | 0 ~ +60℃ |
| Ingress protection (probe) | IP68 |
| Storage condition | 10-60℃ @ 20%-90%RH |
| Process connection options | G3/4 (upper), NPT3/4 (upper and lower threads), 50.5 Chuck |
| Sealing method | End face seal (G3/4), Thread seal (NPT3/4), Gasket (50.5 Chuck) |
| Cable outlet options | M16 connector, Direct line |
| Cable length | 5m default, customizable |
DIMENSION & Installation Notes
Uint:mm
●Regardless of the installation method used, ensure no air bubbles accumulate near the measuring electrodes.
●If selecting the M16 aviation plug for cable outlet, maintain a minimum straight section length of 70 mm at the outlet end to prevent cable damage or core wire breakage caused by an insufficient bending radius.